GE 029.381539/00 Industrial Control Module (Reuter-Stokes UV Flame Detector Unit)
The GE 029.381539/00 receives ultraviolet flame signals from the matched 350-003-000 UV flame probe installed in the combustion chamber. It amplifies, filters and performs threshold judgment on weak pulse signals, then outputs discrete and analog signals for flame presence / flame loss to the Mark VI / Mark VIe gas turbine control system to implement combustion protection interlock. In case of combustion chamber flameout, this module quickly triggers a flame loss signal to initiate gas turbine trip protection, preventing explosion hazards caused by accumulation of unburnt fuel. As a critical safety component of the gas turbine FSSS (Fuel Safety System), it complies with SIL2 safety integrity level per IEC61508.

Technical Specifications
| Item | Parameter |
|---|---|
| Model | 029.381539/00 |
| Brand | GE (Reuter-Stokes) |
| Matched Probe | 350-003-000 UV Flame Detector |
| Power Supply | 115VAC ±10%, 400Hz |
| Input Signal | Weak photocurrent pulse signal from UV probe |
| Output Signal | Relay dry contacts (flame on / flame loss); optional 4–20mA analog signal for flame intensity |
| Typical Response Time | <500ms |
| Flameout Delay | 1~5s adjustable (field configuration) |
| Protection Class | IP54 |
| Operating Ambient Temperature | -20℃ ~ +70℃ |
| Mounting | DIN rail mounting / panel mounting, installed in local gas turbine control cabinet |
| Applicable Units | GE Frame 9E, Frame 9F heavy-duty gas turbines |
| Safety Certification | Compliant with IEC and NEMA industrial standards, suitable for SIL2 safety loops |
Key Features
- UV Spectrum Discrimination: Detects only flame-specific ultraviolet wavelengths. It effectively rejects high-temperature infrared radiation from the furnace, furnace reflection and ambient electromagnetic interference to reduce false and missed alarms.
- Adjustable Threshold & Delay: Flame judgment threshold and flameout delay can be configured on-site to adapt to various combustion conditions and avoid false trips triggered by transient signal fluctuations during startup and shutdown.
- Dual Signal Output: Dry contacts for safety interlock protection; 4-20mA analog signal for real-time flame intensity monitoring and trend recording in the host control system.
- Built-in Self-Diagnosis: The module monitors probe wire breakage, power supply abnormality and hardware faults, and sends fault alarms to the gas turbine control system to facilitate predictive maintenance.
- Rugged Industrial Design: Vibration-resistant and EMI-resistant, suitable for high-temperature and strong electromagnetic environments inside gas turbine cabinets in power plants.
Application Scenarios
- GE 9E/9F heavy-duty gas turbine combined cycle power plants
- Gas turbine Fuel Safety System (FSSS)
- Continuous combustion chamber flame monitoring and flameout protection interlock
- Combined heat and power plants, oil & gas captive power gas turbine units