Compatible with the HIMatrix F60 modular system architecture, F60 DI 32 01 can be seamlessly integrated into safety-critical scenarios such as process control, protection systems, burner control and machine control through standardized installation and configuration procedures. It meets SIL 3 safety requirements in compliance with IEC 61508, and can satisfy SIL 4 requirements for railway applications in accordance with EN 50126/50128/50129 standards.Its core value lies in ensuring the reliability and safety of sensor signal acquisition on industrial sites via hardware-based fault detection, anti-interference design and safety state guarantee mechanisms, providing fundamental input support for the safe operation of the entire automation system.

Core Technical Specifications
- Operating temperature: 0°C ~ +60°C (test limit: -10°C ~ +70°C)
- Storage temperature: -40°C ~ +85°C
- Degree of protection: IP20 (higher protection such as IP54 can be achieved with system cabinet)
- Pollution degree: Class II (in accordance with IEC/EN 61131-2)
- Maximum altitude: < 2000 m
- ESD protection: 6 kV contact discharge, 8 kV air discharge (IEC/EN 61000-4-2)
- Surge protection: 2 kV common mode / 1 kV differential mode for signal lines (IEC/EN 61000-4-5)
- RF immunity: 20 V/m in 80 MHz~1 GHz band (IEC/EN 61000-4-3)
- Dimensions: 6 rack units (RU), height 262 mm, suitable for F60 standard subrack
- Mounting: Horizontal DIN‑rail or panel mounting; freely configurable in subrack slots 3 to n (Slot 1: power module, Slot 2: CPU module)
- Connection: Front‑mounted pluggable terminals, suitable for cables up to 6 mm

Key Features and Benefits
- High Safety IntegrityDesigned in accordance with the de‑energize to trip principle. Input channels automatically switch to a safe state in the event of a fault, with safety functions maintained independently of external power. Supports integration with safety‑related communication protocols such as SafeEthernet, ensuring secure signal transmission.
- Powerful Fault DetectionEquipped with a line control function that allows direct connection to safety devices (e.g., emergency stop buttons) complying with EN 954‑1 Category 4. In case of a fault, multi‑level alarms are activated: ERROR LED flashing, input set to 0, and error code generation, enabling fast troubleshooting.
- Anti‑Interference & Stable DesignFeatures noise blanking (signals must be valid for more than two cycles to be recognized), preventing misinterpretation of surge pulses as valid signals per EN 61000‑4‑5. The front of the module is fitted with channel status LEDs for direct visual indication of each channel’s operating state.
- Flexible CompatibilityCompatible with two programming tools:
- SILworX (for CPU‑OS V7 and later)
- ELOP II Factory (for CPU‑OS earlier than V7)Supports seamless communication with other modules and remote I/O in the HIMatrix series, and allows mixed networking with different operating system versions (with some restrictions).
- Easy MaintenanceSupports online diagnostics and fault query; channel fault history, module temperature, and other data can be read via programming tools. The module supports hot‑swap (subject to shutdown procedures), and no re‑configuration of system ID or IP address is required after replacement.

- F60 CPU 01 Processor Module (provides system computing and safety logic execution)
- PS 01 Power Supply Module (provides 24 VDC power supply and backup battery)
- F60 DO 8 01 Digital Output Module
- F60 DIO 24/16 01 Digital Input/Output Combination Module
- F60 AIO 8/4 01 Analog Input/Output Module
- PROFIBUS DP Master/Slave Module
- Modbus Master/Slave Module
- SafeEthernet Communication Module (supports cross-device safety communication)
- SILworX Programming Software (for CPU-OS V7 and later)
- ELOP II Factory Programming Software (for CPU-OS versions below V7)
- PADT Debugging Computer (with corresponding programming tools installed)
- F60 Subrack
- Rail mounting kit
- Shielding clamps
- Terminals
- Safety earthing components

- F60 DI 16 01: 16-channel digital input module, suitable for small-point signal acquisition. It has the same dimensions and installation method as the DI 32 01.
- F60 DI 64 01: 64-channel digital input module, a high-density signal acquisition solution for large-scale sensor network applications.
- F60 DI 32 02: Enhanced 32-channel digital input module, supporting faster signal response speed and more comprehensive fault diagnosis functions.
- HIMatrix F30 DI 32 01: Compact 32-channel digital input module designed for the HIMatrix F30 compact system. It can communicate with the F60 system via SafeEthernet.
- F60 DI 24 01: 24-channel digital input module, balancing channel count and cost, suitable for medium-scale safety control applications.











3005319639